INPUT |
Nominal Voltage | 110VAC / 127VAC / 208VAC / 220VAC / 230VAC / 240VAC |
Input voltage tolerance | ± %15 |
Nominal frequency | 50Hz / 60Hz |
Transformer | Galvanically isolated |
ITHD | < 45-50% Standard |
Input Protection | Thermic Magnetic Overcurrent protection MCB, Overvoltage protection |
OUTPUT |
Output Voltage | 24 VDC / 48 VDC / 110 VDC / 220 VDC |
Output voltage adjustment | 100% - 120% of Nominal Output Voltage |
Output current adjustment | 10% - 100% of Nominal Output Current |
Battery charging current adjustment | 10% - 100 % of Nominal Output Current |
Boost charger voltage | 100% - 120% of Floating Output Current |
Boost voltage(V/C) | 2,4 Lead Acid Battery 1,60 NiCd Battery |
Float voltage(V/C) | 2,23 Lead Acid Battery 1,40 NiCd Battery |
Nominal output current | 10A to 10000A |
Maximum output current | 100 % of Nominal Output Current |
Filtering | L-C Filtre |
GENEL |
Boost timer | 0-600 hours adjustable |
Cooling | Fan forced cooling (Standard), Natural cooling (Optional) |
Isolation voltage | 1500 or 3000VAC input/chassis and output/chassis |
Efficiency at full load | > 80% |
Protection class | IP20 (Standard); IP21 - IP54 (Optional), (Consult for IP54 to IP65) |
Cable entry | Front bottom (Top entry, optional) |
Access to batteries | Batteries and rectifier in the same cabinet with front access (Optional) |
Circuit breakers | Thermic-magnetic circuit breakers for input, output and battery |
Reset button | Auto start |
Measurements | Load output voltage and current / Batt.. output voltage and current / Utility voltage / Line voltage / Frequency / Power factor (Optional) / Batt. ambient temperature (Optional) |
ENVIRONMENTAL DATA |
Acoustic Noise | 45 - 55 dB (according to power rating) |
Storage temperature | (-20°C) - (+70°C) |
Operating temperature | (-5°C) - (+50°C) |
Relative humidity | 0 - 95% Non-condensing |
Altitude | 1000m (-1% Power for every 100m aſter 1000m) Max. 4000m |
Color | RAL7035, RAL7032 (Standard), others (Optional) |
COMMUNICATION & PARALLELING |
Communication | RS232 (Standard), Dry Contacts (Standard), RS485 (Optional), Modbus TCP (Optional), SNMP (Optional), GSM (Optional) |
Paralleling | Parallel Redundant (No need for extra kit for paralleling) |
STANDARTLAR |
Standards | IEC62040-1, IEC62040-2, ISO9001, ISO14001 |