TECHNICIAL SPECIFICATIONS |
Capacity | 6 kVA / 6 kW |
INPUT |
Input wiring | Single-phase three-wire (16 + N + PE) |
Voltage | 208 / 220 / 230 / 240 Vac |
Voltage range | 110 - 176 Vac (linear derating between 50% and 100% load); 176 - 288 Vac (no derating) |
Frequency | 50/60Hz (auto-sensing) |
Frequency range | 40 ~ 70 Hz |
Power factor | 0.99 |
Bypass voltage range | - 40% ~ +15% (settable) |
THDI | ≤ %5 |
OUTPUT |
Output wiring | Single-phase (L- N) |
Voltage | 208 (PF= 0.9) / 220 / 230 / 240 Vac |
Voltage regulation | ± %1 |
Frequency | Synchronized to bypas s in mains mode; 50/60 Hz + 0.1%Hz in battery mode |
Waveform | Sinusoidal |
Power factor | 1.0 |
THD | ≤ 1% (linear load); ≤ 4% (non-linear load); |
Output current crest factor | 3:1 |
Overload | 105% - 110% for 10 min, 110% - 125% for 1 min, 126% - 150% for 30 s |
BATTERIES |
DC Voltage | 192 Vdc (192-240 Vdc settable) |
Battery Number | 16 pcs (16 - 20 settable) |
Inbuilt battery (standard model) | 12V / 7Ah x 16 |
Charging current | Standard model: 1 A; Long time model: 5 A (default), 1 - 5 A settable, 12 A (optional; PF 0.9) |
Recharge Time | Standard model: 90% capacity restored in 8 hours; Long time model: depend on the capacity of battery |
SYSTEM |
Efficiency | 94% at 100% load, max. 94.5% at 60% load, a 98% in ECO mode |
Transfer time | 0 ms |
Protection | Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure |
Max. number of parallel connections | 4 |
Communication | RS232 (standard), USB / RS485 / dry contacts / SNMP/ battery temperature compensation (optional) |
Display | LCD + LED |
GENEL |
Operating temperature | 0°C ~ 40°C |
Storage temperature | -25°C ~ 55°C (without battery) |
Relative humidity | 0 - 95% (non-condensing) |
Height | ≤ 1000 m, debating 1% for each additional 100 m |
IP class | IP 20 |
Noise level | ≤ 55 dB |
Dimension (mm) HxWxD | 88x440x580 (H) (*) 176x440x660 (S) (*) |
Packed dimensions (mm) WxDxH | 168x514x696 (H) (*) 418x554x792 (S) (*) |
Weight (kg) | 12 (H), 58 (S) |
Gross weight (kg) | 14 (H), 68 (S) |
(*) | S means standard model; H means long time model. |